SIG200-0A0412200 - 1089794

    This combination does not exist.

    Buy Now

    Features
    Product category IO-Link Master
    Supported products

    IO-Link Devices

    Binary actuators

    Binary switching sensors
    Further functions

    Web server integrated

    USB connection for easy configuration of the SIG200 Sensor Integration Gateway with SOPAS ET, the engineering tool from SICK

    Logic editor is available for easy configuration of logic functions
    Items supplied SIG200-0A0412200, 4x blind plugs (M12) on port S2, S3, S4, P2, 1x blind plug (M8) on port CONFIG, Marking labels, quickstart

    Mechanics/electronics
    Connections
    IO-Link 4 x M12, 5-pin female connector, A-coded
    Power 1 x M12, 4-pin plug, A-coded
    CONFIG 1 x M8, 4-pin female connector, USB 2.0 (USB-A)
    Ethernet 2 x M12, 4-pin female connector, D-coded
    Power voltage supply
    Supply voltage 10 V DC ... 30 V DC 1)
    Current consumption
    ≤ 175 mA (At supply voltage 24 V DC) 2)
    ≤ 3,000 mA 3)
    Optical indicators

    4 LED green (To the IO-Link ports, Pin4 (C/DI/DO))

    4 LED yellow (To the IO-Link ports, Pin2 (DI))

    2 LED green (To the Ethernet ports)

    1 LED green (For the Power Port)

    2 LED dual-color
    Input/output characteristics
    S1-S4 pin 1 voltage supply ≤ 500 mA
    S1-S4 pin 4 output current ≤ 200 mA 4)
    Power Port pin 4 output voltage HIGH VH ≥ VUS - 3 V
    S1-S4 pin 2 input voltage Type 3 IEC 61131-2
    S1-S4 pin 4 input voltage Type 1 IEC 61131-2
    Enclosure rating IP67
    Protection class III
    Housing material Zinc
    Housing color Light blue/Black
    Weight 520 g
    Dimensions (L x W x H) 213.9 mm x 57 mm x 38.3 mm
    UL File No. E497722
    1) 10 - 30 V DC without IO-Link, 18 - 30 V DC with IO-Link.
    2) Without sensors, outputs switched off.
    3) The sum of all outputs, including the digital outputs, must not exceed the maximum current consumption of the device. The current consumption must be limited.
    4) Pin 4 configured as digital output. The maximum output current does not depend on the voltage supply at pin 1 of S1-S4.

    Interfaces
    Communication interface IO-Link, USB, Ethernet, PROFINET, REST API
    Logic editor ✔
    Web server ✔
    IO-Link Master
    Function The SIG200 Sensor Integration Gateway is an IO-Link master with 4 configurable ports to which IO-Link device as well as binary switching sensors and actuators can be connected. The gateway data is made available to a PLC or cloud application via the REST API.
    SIG200 can also be operated as a standalone system by directly configuring simple logic functions across several connected devices via the SOPAS ET user interface.
    IO-Link version V1.1, V1.0
    Port Class A
    Number of IO-Link ports 4
    Transmission type COM1, COM2, COM3
    Operator interfaces SOPAS ET, the engineering tool for configuration via USB, Additionally, the SIG200 can be configured via the integrated webserver. Default IP adress: 192.168.0.1
    MAC address See product label
    Number of inputs Max. 8 x PNP, type 1 or 4 x IO-Link
    Number of outputs Max. 4 x PNP
    Max. Output frequency 50 Hz
    Inputs/outputs
    S1-S4 4 configurable ports
    Pin4 can be used in one of the available port modes: IO-Link, digital input or digital output.
    An additional digital input signal can be connected using Pin2.
    LINK/ACT 1 & 2 Two Ethernet ports are provided for the network connection
    CONFIG Port for configuration via USB with SOPAS ET (SOPAS ET can be downloaded for free from www.sick.com)
    Conformities Conformance Class B
    Network load class III
    Initialization time after switch on 60s (plus additional time for IODD installation)

    Ambient data
    Ambient operating temperature –40 °C ... +55 °C 1)
    Ambient temperature, storage –40 °C ... +75 °C 1)
    Electromagnetic compatibility (EMC)

    EN 61000-6-2:2005-08

    EN 61000-6-3:2007-01
    Shock load EN 60068-2-6