QUINT-DIODE/40 - 2938963
DC operation
Input voltage 24 V DC
Nominal input voltage range 24 V DC
Input voltage range 0 V DC ... 30 V DC
Input voltage range DC 0 V DC ... 30 V DC
Voltage type of supply voltage DC
Reverse polarity protection < yes60 V
Nominal input current (IN) 2x 20 A
Transient surge protection Transil diode
Voltage drop, input/output 0.5 V
Output data
Efficiency > 97 %
Nominal output voltage 24 V DC
Output voltage UIn -
Nominal output current (IN) 40 A
Power loss nominal load max. 20 W
Connection in series No
Terms and Conditions
30-day money-back guarantee
Shipping: Contact us info@aarkautomation.com
Product Details
DC operation | |
Input voltage | 24 V DC |
Nominal input voltage range | 24 V DC |
Input voltage range | 0 V DC ... 30 V DC |
Input voltage range DC | 0 V DC ... 30 V DC |
Voltage type of supply voltage | DC |
Reverse polarity protection | < yes60 V |
Nominal input current (IN) | 2x 20 A |
1x 40 A | |
Maximum current Imax | 2x 19 A (6 mm² at 40°C) |
1x 39 A (6 mm² at 40°C) | |
2x 16 A (6 mm² at 60°C) | |
1x 32 A (6 mm² at 60°C) | |
2x 27 A (10 mm² at 40°C) | |
1x 54 A (10 mm² at 40°C) | |
2x 21 A (10 mm² at 60°C) | |
1x 43 A (10 mm² at 60°C) | |
2x 30 A (16 mm² at 40 °C) | |
1x 60 A (16 mm² at 40 °C) | |
2x 24 A (16 mm² at 60°C) | |
1x 48 A (16 mm² at 60°C) | |
Transient surge protection | Transil diode |
Voltage drop, input/output | 0.5 V |
Efficiency | > 97 % |
Nominal output voltage | 24 V DC |
Output voltage | UIn - |
Nominal output current (IN) | 40 A |
Power loss nominal load max. | 20 W |
Connection in series | No |
Input | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.5 mm² |
Conductor cross section solid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Stripping length | 10 mm |
Screw thread | M4 |
Output | |
Connection method | Screw connection |
Conductor cross section solid min. | 0.5 mm² |
Conductor cross section solid max. | 16 mm² |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 10 mm² |
Conductor cross section AWG min. | 20 |
Conductor cross section AWG max. | 6 |
Stripping length | 10 mm |
Screw thread | M4 |
Insulation voltage output / PE | 1 kV |
Insulation voltage input / PE | 1 kV |
Insulation voltage input, output / housing | 1 kV |
Product type | Redundancy module |
MTBF (IEC 61709, SN 29500) | 28571428 h (40 °C) |
Insulation characteristics | |
Protection class | II (in closed control cabinet) |
Degree of pollution | 2 |