DC/DC converters - QUINT-PS/24DC/24DC/ 5 - 2320034

    This combination does not exist.

    Buy Now

    Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 24 V DC, output: 24 V DC/5 A


    Terms and Conditions
    30-day money-back guarantee
    Shipping: Contact us info@aarkautomation.com


    DC/DC converters - QUINT-PS/24DC/24DC/ 5
    2320034

    Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 24 V DC, output: 24 V DC/5 A

    In stock
    Expected to leave our warehouse in India on 18-May-2022, if ordered now

    Product Details


    QUINT DC/DC converter with maximum functionality
    DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation.
    QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.



    DC operation
    Nominal input voltage range 24 V DC
    Input voltage range 18 V DC ... 32 V DC
    Extended input voltage range in operation 14 V DC ... 18 V DC (Derating)
    Wide-range input no
    Input voltage range DC 18 V DC ... 32 V DC
    14 V DC ... 18 V DC (Consider derating during operation)
    Inrush current < 15 A (typical)
    Inrush current integral (I2t) < 0.5 A2s
    Mains buffering time > 10 ms (24 V DC)
    Current consumption 7 A (24 V, IBOOST)
    Reverse polarity protection ≤ yes30 V DC
    Protective circuit Transient surge protection; Varistor
    Input fuse 15 A (internal (device protection))
    Recommended breaker for input protection 10 A ... 16 A (Characteristics B, C, D, K)

    Efficiency > 92 %
    Output characteristic U/I
    Nominal output voltage 24 V DC ±1 %
    Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
    Nominal output current (IN) 5 A (-25 °C ... 60 °C)
    POWER BOOST (IBoost) 6.25 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
    Selective Fuse Breaking (ISFB) 30 A (12 ms)
    Magnetic circuit breaker tripping B2 / B4 / C2
    Derating 60 °C ... 70 °C (2.5%/K)
    Feedback voltage resistance 35 V DC
    Protection against overvoltage at the output (OVP) < 35 V DC
    Max. capacitive load unlimited
    Active current limitation Approximately 7.2 A
    Control deviation < 1 % (change in load, static 10 % ... 90 %)
    < 2 % (change in load, dynamic 10 % ... 90 %)
    < 0.1 % (change in input voltage ±10 %)
    Residual ripple < 20 mVPP
    Output power 120 W
    Peak switching voltages nominal load < 10 mVPP (20 MHz)
    Maximum no-load power dissipation 2.4 W
    Power loss nominal load max. 11.4 W
    Rise time < 2 ms (UOUT (10 % ... 90 %))
    Connection in parallel yes, for redundancy and increased capacity
    Connection in series yes
    Connection in series 2 (Devices)
    Signal: DC OK active
    Output description UOUT > 0.9 x UN: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: POWER BOOST, active
    Output description IOUT < IN: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: UIN OK, active
    Output description UIN > 19.2 V: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: DC OK active
    Output description UOUT > 0.9 x UN: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: POWER BOOST, active
    Output description IOUT < IN: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: UIN OK, active
    Output description UIN > 19.2 V: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: DC OK active
    Output description UOUT > 0.9 x UN: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: POWER BOOST, active
    Output description IOUT < IN: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)
    Signal: UIN OK, active
    Output description UIN > 19.2 V: High signal
    Switching voltage range 18 V DC ... 24 V DC
    Maximum inrush current < 20 mA (short-circuit-proof)

    Input
    Connection method Pluggable screw connection
    Conductor cross section solid min. 0.2 mm²
    Conductor cross section solid max. 2.5 mm²
    Conductor cross section flexible min. 0.2 mm²
    Conductor cross section flexible max. 2.5 mm²
    Conductor cross section AWG min. 24
    Conductor cross section AWG max. 12
    Stripping length 8 mm
    Screw thread M3
    Tightening torque, min 0.5 Nm
    Tightening torque max 0.6 Nm
    Output
    Connection method Pluggable screw connection
    Conductor cross section solid min. 0.2 mm²
    Conductor cross section solid max. 2.5 mm²
    Conductor cross section flexible min. 0.2 mm²
    Conductor cross section flexible max. 2.5 mm²
    Conductor cross section AWG min. 24
    Conductor cross section AWG max. 12
    Stripping length 7 mm
    Screw thread M3
    Tightening torque, min 0.5 Nm
    Tightening torque max 0.6 Nm
    Signal
    Conductor cross section solid min. 0.2 mm²
    Conductor cross section solid max. 2.5 mm²
    Conductor cross section flexible min. 0.2 mm²
    Conductor cross section flexible max. 2.5 mm²
    Conductor cross section AWG min. 24
    Conductor cross section AWG max. 12
    Screw thread M3
    Tightening torque, min 0.5 Nm
    Tightening torque max 0.6 Nm

    Types of signaling LED
    Active switching output
    Relay contact
    Signal output: DC OK active
    Status display "DC OK" LED green
    Color green
    Signal output: POWER BOOST, active
    Status display "BOOST" LED yellow/IOUT > IN : LED on
    Color yellow
    Note on status display LED on
    Signal output: UIN OK, active
    Status display LED "UIN < 19.2 V" yellow/UIN < 19.2 V DC: LED on
    Color yellow
    Note on status display LED on

    Number of phases 1.00
    Insulation voltage input/output 1.5 kV (type test)
    1 kV (routine test)
    Insulation voltage input/output 1 kV (type test)

    Product type DC/DC converters
    MTBF (IEC 61709, SN 29500) > 890000 h (40 °C)
    Insulation characteristics
    Protection class III
    Degree of pollution 2

    Width 32 mm
    Height 130 mm
    Depth 125 mm
    Installation dimensions
    Installation distance right/left 0 mm / 0 mm (≤ 70 °C)
    Installation distance right/left (active) 15 mm / 15 mm (≤ 70 °C)
    Installation distance top/bottom 50 mm / 50 mm (≤ 70 °C)
    Installation distance top/bottom (active) 50 mm / 50 mm (≤ 70 °C)
    Alternative assembly
    Width 122 mm
    Height 130 mm
    Depth 35 mm